| Customization: | Available |
|---|---|
| Phase: | Three Phase |
| Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| APlus Modular UPS Selection Guide | ||||||||
| MODEL | A+30U-120 | A+30U-180 | A+42U-300 | A+42U-420 | A+42U-480 | A+42U-600 | ||
| PHASE | 3-phase in /3-phase out | |||||||
| CABINET CAPACITY* | 120 KW | 180 KW | 300 KW | 420KW | 480KW | 600KW | ||
| BATTERY TYPE | Extemal Battery | |||||||
| ONE POWER MODULE CAPACTY | 60KVA/60KW | |||||||
| MAX.POWER MODULE NO | 2 | 3 | 5 | 7 | 8 | 10 | ||
| INPUT | ||||||||
| Nominal Voltag | 3x380/400/415 VAC (3Ph+N) | |||||||
| Voltage Range | 30%~+20% | |||||||
| Nominal Frequency | 50/60Hz(Auto Sensing) | |||||||
| Frequency Range | 40Hz~70Hz | |||||||
| Power Facto | >0.99 @100%Load,>0.98 @50%Load | |||||||
| Harmonic Distortion (THDi) | <3%@100%load | |||||||
| OUTPUT | ||||||||
| Nominal Voltage | 3x380/400/415 VAC (3Ph+N) | |||||||
| Voltage Regulation(Steady state) | ≤±1%Typical (balanced load);≤±2%Typical (unbalanced load) | |||||||
| Nominal Frequency | 50/60Hz | |||||||
| Frequency Range(Synchronized) | 46Hz~54Hz or 56Hz~64Hz | |||||||
| Overdoad Capability | 1 hour for ≤110%,10 mins for 111%~125%,1 min for 126%~150%and 200ms for>150% | |||||||
| Harmonic Distortion | ≤2%THD(Linear Load);≤4%THD(Non-linear Load) | |||||||
| Eficiency | 96% | |||||||
| BATTERY/CHARGER | ||||||||
| Nominal Voltage | +1-192V~+1-240V (Selectable) | |||||||
| Maximum Voltage | +/-240V (12Vx40 Pcs | |||||||
| Minimum Voltage | +/-192V(12Vx32 Pcs) | |||||||
| Floating Charge Voltage | 2.28V/Cell (2.25~2.33 Selectable) | |||||||
| Boost Charging Voltage | 2.35V/Cell | |||||||
| Temperature Compensation | Yes | |||||||
| Maximum Charging Current (Per Power Module) |
18A(Adjustable) | |||||||
| PHYSICAL | ||||||||
| Cabinet Dimension (DxWxH)mm | 1100x600x1475 | 1100x600x1475 | 1100x600x2010 | 1100x600x2010 | 1065x1000x2000 | 1065x1000x2000 | ||
| Net Weight (Kg) | 308 | 352 | 516 | 654 | 932 | 1020 | ||
| ENVIRONMENT | ||||||||
| Operating Temperature | 0~40°ºC | |||||||
| Relative Humidity | D~958%pon-condensing | |||||||
| Altitude* | <1000m for Nominal power | |||||||
| IP Protection | IP 20 | |||||||
| MANAGEMENT | ||||||||
| Smart RS-232/USB | Supports Windows Family,Linux and MAC | |||||||
| Optional SNMP | Power management from SNMP manager and web browser | |||||||
| STANDARDS | ||||||||
| Safety | IEC/EN 62040-1 | |||||||
| EMC | IEC/EN 62040-2 Category C3 | |||||||
| "If the UPS is installed or used in a placewhere the altitude is above than 1000m,the output power must be derated one percent per 100m Product specifications are subject to change without further notice. |
||||||||
| Model | Description | Dimension DxWxH(mm) | Weight (kg) | |||||
| PM-60 | 3P/3P 60KVA/60KW power module | 750x438x130 (3U) | 44 | |||||