| Rated Power (kVA/kW)* | 250 kVA/250 kW | 300 kVA/300 kW | 400 kVA/400 kW | 500 kVA/500 kW | 600 kVA/600 kW |
| Input | |||||
| nput voltage (V) | 380/400/415V(3-phase +Neutral +PE) | ||||
| Frequency (Hz) | 40-70 Hz | ||||
| nput power factor | >0.99 | ||||
| THD | <3% | ||||
| Input voltage range | 323-477V | ||||
| Dual mains inpu | Yes (default:single mains input) | ||||
| Outpu | |||||
| Parallel | Up to 5 UPSs for capacity (or 5+1 for redundancy) | ||||
| Nominal output voltage (V) | 380/400/415V | ||||
| Efficiency:Double conversion mode | Up to 96% | ||||
| ECO mode | 99% | ||||
| Overload capacity in normal operation | 150%for 1 minute,125%for 10 minutes,105%continuous | ||||
| Output voltage tolerance | +/-1% | ||||
| Load Power Factor compatibility | From 0.5 leading to 0.5 lagging | ||||
| Communication and management | |||||
| Communication interface | RS485,dry contacts,Ethernet (SNMP,Modbus,TCP/IP,BACnet) | ||||
| Control panel | 7-inch touchscreen LCD,status,and display console | ||||
| Weights and dimensions | |||||
| UPS,unpackaged/dimensions (H × W × D) | 1970x600x850mm | 1970x1000x850 mm | |||
| UPS,unpackaged weight | 425 kg | 465 kg 560 kg | 640kg | 720 k | |
| Raalatop, | |||||
| Safety | EC/EN 62040-1 | ||||
| EMC | EC/EN 62040-2 | ||||
| Performance | EC/EN 62040-3 | ||||
| Markin | CE | ||||
| Raitery tyee | |||||
| Battery type | VRLA | ||||
| Number of batteries | 36-50 | ||||
| Charging power in %of output power (selectable) |
26% | 24% | |||
| Environmental | |||||
| Relative humidity | 0 to 95%non-condensing | ||||
| Operating elevation | 0 to 1500 m without derating | ||||
| Audible noise at 1m from unit | 70db | 72db | |||
| Protection class | IP20 (IP31 with optional kit) | ||||