Customization: | Available |
---|---|
Type: | Cabinet Air Conditioner |
Air Tube Material: | Galvanized Sheet |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical parameters and configuration table of precision air conditioners for small computer rooms | |||||
Category | Constant temperature and humidity type | ||||
Indoor unit model | CNA1008F3Z3A | CNA1013F3Z3A | CNA1017F3Z3A | CNA1020F3Z3A | |
Outdoor unit model | CST008SP1A | CST013SP1A | CST017SP1A | CST020SP1A | |
Energy efficiency ratio | 3.0 | 3.0 | 3.0 | 3.0 | |
Power supply specification | 380VAC/50HZ | ||||
Indoor unit maximum current | 11.5A | 15.5A | |||
Outdoor unit maximum current | 1.1A | 2.2A | |||
Recommended input air switch | 25A/4P | 25A/4P | |||
Indoor unit cable (recommended) | 5*2.5mm2 | 5*4mm2 | |||
Outdoor unit cable (recommended) | 3*1mm2 | 3*1mm2 | |||
Indoor and outdoor unit signal line (recommended) | None | ||||
Cooling capacity (kW) | 7.5 | 12.5 | |||
Sensible cooling capacity (kW) | 6.9 | 11.5 | |||
Sensible heat ratio | 0.92 | 0.92 | |||
Supply air volume (m3/h) | 2200 | 3000 | |||
Return air volume (m3/h) | 2200 | 3000 | |||
Heat exchange capacity (kw) | 11 | 18 | |||
PTC electric heating power (kW) | 3 | 3 | |||
Electrode humidification capacity (kg/h) | 3 | 3 | |||
Compressor | Number of compressors | 1 | |||
Fixed frequency/Frequency conversion | Fixed frequency | ||||
Compressor type | Highly rotor compressor | ||||
Indoor fan | Air supply method | Upward air supply | |||
Number of fans | 1 | ||||
Fan type | Cross-flow fan | ||||
Outdoor fan | Number of fans | 1 | 2 | 2 | 2 |
Fan type | Axial fan | ||||
Evaporator type | Large area "/" type evaporator | ||||
Expansion valve | Type | Thermal expansion valve/Electronic expansion valve | |||
Filter | Filter level | Medium and high efficiency: G4 level | |||
Refrigerant (Copper tube within 5 meters can be used) | Type | R410A | |||
Indoor unit factory pre-charge (kg) | 1 | 1.5 | |||
Outdoor unit factory pre-charge (kg) | 1 | 1.5 | |||
Noise level (dB) | Indoor unit | 56.5 | 60 | ||
Outdoor unit | 57 | 61 | |||
Dimensions (mm) | Indoor unit(W*D*H) | 500*500*1740 | 700*500*1740 | ||
Outdoor unit(W*D*H) | 850*400*730 | 1200*400*730 | |||
Weight (kg) | Indoor unit | 130 | 170 | ||
Outdoor unit | 59.5 | 61 | |||
Recommended pipe size (mm) | Air pipe | 12.7 (Coil pipe) | 16 (Coil pipe) | ||
Liquid pipe | 9.52 (Coil pipe) | 9.52 (Coil pipe) | |||
Water inlet pipe (constant temperature and humidity) | G1/2" | ||||
Drain pipe | IDΦ19mm | IDΦ22mm | |||
Allowable pipe length (m) | Equivalent length of internal and external machine pipes | <20 (If the project exceeds the requirements, contact the local pre-sales engineer) | |||
Difference in installation position of internal and external machine | Outdoor unit higher than indoor unit: ≤10 (If the project exceeds the requirements, contact the local pre-sales engineer) | ||||
Outdoor unit lower than indoor unit: ≤5 (If the project exceeds the requirements, contact the local pre-sales engineer) | |||||
Design and use conditions | Indoor ambient temperature 24ºC/wet bulb temperature 17ºC; outdoor ambient temperature 35ºC. | ||||
Standard (functional) parts | Sight glass, high/low pressure protection switch, high pressure sensor, filter pressure differential switch. | ||||
Optional (functional) parts | 1. Extension components (configured for single-way pipelines with a length exceeding 20 meters, an oil storage bend needs to be added every 5 to 7.5 meters), with a maximum extension of 30 meters; 2. Low-temperature components (configured for areas with outdoor temperatures below -15°C), which can reach -35°C after configuration. | ||||
Product features | 1. 4.3-inch touch screen; 2. Power-off memory, automatic start-up when receiving a call; 3. Group control networking (up to 32 units); 4. Intelligent protection: power phase loss, over-voltage, under-voltage, reverse phase protection alarm, compressor high and low pressure protection alarm, room environment high/low temperature alarm; 5. Monitor and display the operating status of the outdoor unit: condensing pressure, fan speed, etc.; 6. 500 historical records can be stored. |