Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated Capacity(KVA) | 30 | 40 | 60 | 80 | |||||||
Specifications | |||||||||||
Size(W*D*Hmm) | 440*1000*1600 | 600*1000*1600 | |||||||||
Weight(kg) | 245 | 245 | 275 | 295 | |||||||
Input characteristics (rectifier) | |||||||||||
Rated input voltage | 380/400/415VAC,Three-phase four-wire | ||||||||||
Rated operating frequency | 50/60Hz | ||||||||||
Input voltage range | 228~475V | ||||||||||
Input power factor | >0.99 | ||||||||||
THDi | <3% | ||||||||||
Output characteristics (inverter) | |||||||||||
Inverter output voltage | 380/400/415VAC, Three-phase four-wire | ||||||||||
Output power factor | 1 | ||||||||||
Voltage stability | Steady state | 1% <± | |||||||||
Voltage stability | Transient | 5% <± | |||||||||
Bypass | |||||||||||
Bypass input voltage | 380/400/415VAC,Three-phase four-wire | ||||||||||
Bypass voltage range | -0.40~+20% | ||||||||||
System | |||||||||||
Frequency | 50/60Hz | ||||||||||
Mains power synchronization tracking range | ±3HzCan be set within the range | ||||||||||
System efficiency | Reach up to 96.5% | ||||||||||
Working environment | |||||||||||
Operating temperature range | 0~40ºC | ||||||||||
Storage temperature | -40 ~+ 70(without battery) | ||||||||||
Relative humidity | 5%~95%,No condensation | ||||||||||
Maximum operating height | ≤Altitude 1500m, for every 100m added between 1500 and 3000m, the load carried is reduced by 1% | ||||||||||
Noise( 1m) | <60dB | ||||||||||
Protection level | IP20(IP31) | ||||||||||
Standards compliant | Safety: IEC60950-1,IEC62040-1/AS62040-1; Electromagnetic Compatibility:
IEC62040-2/AS62040-2; Design and testing: IEC62040-3/AS62040-3,YD/T1095
|