Customization: | Available |
---|---|
Type: | Cabinet Air Conditioner |
Air Tube Material: | Galvanized Sheet |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Base station air conditioning technical parameters and configuration table | |||||
Category | Single-cooled type | Constant temperature and humidity type | |||
Indoor unit model | EFB008ABT004 (EFB008C1Y0B) |
EFB013ABT004 (EFB013C1Y0B) |
EFB008ABTNN4 (EFB008C6Y0B) |
EFB013ABTNN4 (EFB013C6Y0B) |
|
Outdoor unit model | ECB012 | ECB019 | ECB012 | ECB019 | |
Energy efficiency ratio | 3.6 | 3.45 | 3.6 | 3.45 | |
Power supply specification | 380VAC/50HZ | ||||
Indoor unit maximum current | 7A | 12A | 11.5A | 15A | |
Outdoor unit maximum current | 0.85A | 1.7A | 0.85A | 1.7A | |
Recommended input air switch | 16A/4P | 16A/4P | 16A/4P | 25A/4P | |
Indoor unit cable (recommended) | 5*2.5mm2 | 5*2.5mm2 | 5*2.5mm2 | 5*4.0mm2 | |
Outdoor unit cable (recommended) | 3*1mm2 | ||||
Indoor and outdoor unit signal line (recommended) | None | ||||
Cooling capacity (kW) | 8 | 13 | 8 | 13 | |
Sensible cooling capacity (kW) | 7.36 | 12.22 | 7.36 | 12.22 | |
Sensible heat ratio | 0.92 | 0.94 | 0.92 | 0.94 | |
Supply air volume (m3/h) | 2800 | 3500 | 2800 | 3500 | |
Return air volume (m3/h) | 2800 | 3500 | 2800 | 3500 | |
Heat exchange capacity (kw) | 11 | 17 | 11 | 17 | |
PTC electric heating power (kW) | / | / | 3 | 3 | |
Electrode humidification capacity (kg/h) | / | / | 3 | 3 | |
Compressor | Number of compressors | 1 | |||
Fixed frequency/Frequency conversion | Frequency conversion | ||||
Compressor type | Highly rotor compressor | ||||
Indoor fan | Air supply method | Upward air supply | |||
Number of fans | 2 | ||||
Fan type | Dual axial flow DC fan | ||||
Outdoor fan | Number of fans | 1 | 2 | 1 | 2 |
Fan type | Axial fan | ||||
Evaporator type | Large area U-shaped evaporator | ||||
Expansion valve | Type | Electronic expansion valve | |||
Filter | Filter level | Medium and high efficiency: G2 level | |||
Refrigerant (Copper tube within 5 meters can be used) | Type | R410A | |||
Indoor unit factory pre-charge (kg) | 1 | 1.5 | 1 | 1.5 | |
Outdoor unit factory pre-charge (kg) | 1 | 1.5 | 1 | 1.5 | |
Noise level (dB) | Indoor unit | 56 | 58 | 56 | 58 |
Outdoor unit | 55 | 60 | 55 | 60 | |
Dimensions (mm) | Indoor unit(W*D*H) | 510*425*1865 | |||
Outdoor unit(W*D*H) | 960*370*810 | 960*370*1260 | 960*370*810 | 960*370*1260 | |
Weight (kg) | Indoor unit | 87 | 102 | 93 | 108 |
Outdoor unit | 34 | 53 | 34 | 53 | |
Recommended pipe size (mm) | Air pipe | 12.7 (Coil pipe) | 16 (Coil pipe) | 12.7 (Coil pipe) | 16 (Coil pipe) |
Liquid pipe | 9.52 (Coil pipe) | 9.52 (Coil pipe) | 9.52 (Coil pipe) | 9.52 (Coil pipe) | |
Water inlet pipe (constant temperature and humidity) | G1/2" | ||||
Drain pipe | IDΦ19mm | ||||
Allowable pipe length (m) | Equivalent length of internal and external machine pipes | <20 (If the project exceeds the requirements, contact the local pre-sales engineer) | |||
Difference in installation position of internal and external machine | Outdoor unit higher than indoor unit: ≤10 (If the project exceeds the requirements, contact the local pre-sales engineer) | ||||
Outdoor unit lower than indoor unit: ≤5 (If the project exceeds the requirements, contact the local pre-sales engineer) | |||||
Design and use conditions | Indoor ambient temperature 24ºC/wet bulb temperature 17ºC; outdoor ambient temperature 35ºC | ||||
Standard (functional) parts | High/low pressure protection switch, pressure sensor | ||||
Optional (functional) parts | 1. Extension components (configured when the one-way pipeline length exceeds 20 meters, an oil storage bend needs to be added every 5 to 7.5 meters), the maximum extension is 30 meters; 2. Low temperature components (configured in areas where the outdoor temperature is below -15ºC), after configuration, it can reach -35ºC. |
||||
Product features | 1. 4.3-inch keypad control screen; 2. Power-off memory, automatic restart when receiving a call; 3. Group control networking (up to 32 units); 4. Intelligent protection: power phase loss, over-voltage, under-voltage, reverse phase protection alarm, compressor high and low pressure protection alarm, machine room environment high/low temperature alarm; 5. Monitor and display the operating status of the outdoor unit: condensing pressure, fan speed, power signal, speed regulation signal, etc.; 6. 500 historical records are stored. |