Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Options for ITA2 UPS | |
Name | Comment |
Options for battery | |
TA BClO020k02 | ITA25-20KVA UPS battery module with 1612V9Ah batteries,3U height,and support for tower /rack-mount |
TA BClO020k02L2 | Power cable between batterymodules |
TA BCl0020k02L3 | Cable connecting battery modules with the UPS |
Monitoring Card | |
485 Card | Used in UPS to upload monitoring information through serial communication |
Temperature Sensor | With LCD display;used for UPS temperature compensation or access of RDU-SIC communication card |
Temperature and Humidity Sensor |
With LCD display;used for UPS temperature compensation or access of RDU-SIC communication card |
POD | |
Standalone POD | UPS output distribution system with maintenance bypass |
1+1 parallel-system POD | UPS output distribution system with maintenance bypass,used for 1+1 parallel system |
Monitoring Software | |
network shutdown | Used for remote automatic shutdown of the server |
Options for system | |
Rail | Used for rack-mounting of UPS,battery module and POD |
Battery Backup Time Table(Battery Module) | |||||||||||
Type | Nmter Battery Modrle |
Backup Time | |||||||||
5kw | 4.5kW | 4kW | 3.5kW | 3kW | ?5kN | 2kW | 15kW | kw | 05kW | ||
5kVA | 1 | 5.5 | 65 | 75 | 9.5 | 1L5 | 15.0 | 20.5 | 300 | 49.5 | 103.5 |
2 | 15.0 | 17.5 | 20.5 | 25.0 | 30.5 | 39.0 | 510 | 70.0 | 108.0 | 235.0 | |
3 | 270 | 310 | 360 | 425 | 51.0 | 63.0 | 80.5 | 1100 | 1770 | 368.5 | |
4 | 39.5 | 450 | 515 | 60.0 | 71.5 | 870 | 104.0 | 156.5 | 246.5 | 5020 | |
5 | 515 | 580 | 66.5 | 770 | 915 | 1115 | 1460 | 203.5 | 316.0 | 6355 | |
6 | 63.5 | 715 | 81.5 | 94.5 | 1115 | 1395 | 1815 | 2505 | 386.0 | 768.5 | |
Type | Number of battery Modrle |
Backup Time | |||||||||
10kW | W | BkW | 7kW | W | EkW | 4kW | 3kW | 2kW | kW | ||
10kVA | 2 | 4.0 | 4.5 | 6.0 | 8.0 | TL5 | 15.0 | 205 | 30.5 | 51.0 | 108.0 |
3 | 8.0 | 9.5 | 11.5 | 14.5 | 21.0 | 270 | 36.0 | 510 | 805 | 1770 | |
4 | 12.5 | 150 | 18.0 | 220 | 31.0 | 39.5 | 515 | 715 | 110.5 | 2465 | |
5 | 18.0 | 210 | 25.0 | 300 | 415 | 515 | 66.5 | 91.5 | 146.0 | 316.0 | |
6 | 23.5 | 270 | 320 | 38.5 | 515 | 63.5 | 815 | L5 | 181.5 | 386.0 | |
Type | Number of battery Modre |
Backup Time | |||||||||
EkW | 14.4kW | 12.8kW | L2kW | 9W | kW | 6AkW | 4.EkW | 32kW | 16kW | ||
16kVA | 4 | 75 | 90 | 10.5 | 13.0 | 16.0 | 210 | 285 | 41.5 | 665 | 1450 |
6 | 14.0 | 16.0 | 19.0 | 24.5 | 28.5 | 36.5 | 48.0 | 66.5 | 104.0 | 233.5 | |
8 | 210 | 24.5 | 28.5 | 34.0 | 415 | 52.0 | 670 | 920 | 1475 | 322.0 | |
10 | 28.5 | 33.0 | 38.5 | 45.5 | 54.5 | 670 | 86.0 | 118.5 | 192.5 | 410.5 | |
12 | 35.5 | 415 | 48.0 | 560 | 670 | 820 | 1050 | 148.5 | 2405 | 498.5 | |
Type | Number of Battery Modrle |
Backup Time | |||||||||
20kW | 18kW | 16kW | 14kw | 12kW | 1OkW | EkW | W | 4kw | 2kW | ||
20kVA | 4 | 5.5 | 6.5 | 75 | 9.5 | 1L5 | 15.0 | 210 | 310 | 515 | 1L0 |
6 | 10.0 | 11.5 | 14.0 | 170 | 210 | 270 | 365 | 51.5 | 815 | 181.5 | |
8 | 15.0 | 17.5 | 210 | 255 | 310 | 39.5 | 52.0 | 72.0 | 112.0 | 252.5 | |
10 | 210 | 24.5 | 285 | 34.0 | 415 | 52.0 | 670 | 92.5 | 148.0 | 324.0 | |
12 | 270 | 3L5 | 36.5 | 430 | 52.0 | 64.0 | 820 | 1125 | 184.0 | 395.0 |
Capacity | 5/6KVA | 10KVA | 16/20KVA |
Input | |||
l/O mode | 1/1 | 1/1,3/1 | 3/1,3/3 |
Voltage Range | 100~288Vac | ||
Freguency Range | 40Hz-70Hz | ||
Current Harmonic | <5% | ||
Power Factor | 0.99 | ||
Batterv-externa | |||
Compatible Battery type | Lead acid,lithium,ni-cd | ||
Charge | <5A(Long back-up model) 2A(Standard model) |
<8A(Long back-up model <4A(Standard model) |
<13A(Long back-up mode) <5A(Standard model) |
Number of cell | 12/16/20,16 by defaul | ±12/±16/±20,±16 by default | |
Output | |||
Rated Power | 5KW/6KW | 10KW | 16KW/20KW |
Ratod Voltage | 220/230/240 Va | ||
Power Factor | 1 | ||
Voltage Stability | 1% | ||
Frequency Stability | ±0.1Hz | ||
Voltage harmonic distortion | <2%(linear load);<4%(non-linear load) | ||
crest tactor | 3:1 | ||
Dynamic voltage Transient range | 5% | ||
Voltage transient recovery time | 60ms | ||
Overload Capacity | 105%~125%load,5min;125%~150%load,1min;>150%load,200ms | ||
Svstem | |||
mounting | Tower/rack | ||
Fficlency | Up to 95.5% | Up to 95.8% | Upto 96% |
FCO Eficiency | 99% | 99% | 99% |
Number of units for parallel system | 4 at most | ||
Switching time (bypass to battery) | 0ms | ||
Switching time Cinverter to bypass) | 0ms | ||
Noise | 55dB | 55dB | 58dB |
Protection Grade | P20 | ||
Size(mm) | 430*85*400 | 430*85*500 | 430*130*500 |
Weight (kg) | 11 | 15 | 23 |
Communication and management | |||
Interface Tvpe | SNMP,USB,RS232,RJ45,dry contact,REPO,intelli-slot,parallel port | ||
Battery Temperature Sensor | Optiona | ||
LCD | 2.8 inch color screen,gravity self-adaption,boot guid | ||
Environmental Parameter | |||
Operating Temperature | 0~50ºC.Output power reduced to 70%in case of 50ºC | ||
Relative Humidity | 0~95% | ||
Max.Altitude Certification &Test |
3000m.No dorating | ||
CE,Energy Star,TLC,COC,seismic technologt,shipping | |||
Rohs,Reach | |||
Wet dust test,fire test,temperature limit test,high altitude test,vehicle loading test |