Technical parameters and configuration table of precision air conditioners for small computer rooms |
Category |
Single-cooled type |
Indoor unit model |
CSA1008F1Z3A |
CSA1013F1Z3A |
CSA1017F1Z3A |
CSA1020F1Z3A |
Outdoor unit model |
CST008SP1A |
CST013SP1A |
CST017SP1A |
CST020SP1A |
Energy efficiency ratio |
3.0 |
3.0 |
3.0 |
3.0 |
Power supply specification |
380VAC/50HZ |
Indoor unit maximum current |
7A |
12A |
|
|
Outdoor unit maximum current |
1.1A |
2.2A |
|
|
Recommended input air switch |
16A/4P |
25A/4P |
|
|
Indoor unit cable (recommended) |
5*2.5mm2 |
5*4mm2 |
|
|
Outdoor unit cable (recommended) |
3*1mm2 |
3*1mm2 |
|
|
Indoor and outdoor unit signal line (recommended) |
None |
Cooling capacity (kW) |
7.5 |
12.5 |
|
|
Sensible cooling capacity (kW) |
6.9 |
11.5 |
|
|
Sensible heat ratio |
0.92 |
0.92 |
|
|
Supply air volume (m3/h) |
2200 |
3000 |
|
|
Return air volume (m3/h) |
2200 |
3000 |
|
|
Heat exchange capacity (kw) |
11 |
18 |
|
|
PTC electric heating power (kW) |
/ |
/ |
/ |
/ |
Electrode humidification capacity (kg/h) |
/ |
/ |
/ |
/ |
Compressor |
Number of compressors |
1 |
Fixed frequency/Frequency conversion |
Fixed frequency |
Compressor type |
Highly rotor compressor |
Indoor fan |
Air supply method |
Upward air supply |
Number of fans |
1 |
Fan type |
EC fan |
Outdoor fan |
Number of fans |
1 |
2 |
2 |
2 |
Fan type |
Axial fan |
Evaporator type |
Large area "/" type evaporator |
Expansion valve |
Type |
Thermal expansion valve/Electronic expansion valve |
Filter |
Filter level |
Medium and high efficiency: G4 level |
Refrigerant (Copper tube within 5 meters can be used) |
Type |
R410A |
Indoor unit factory pre-charge (kg) |
1 |
1.5 |
|
|
Outdoor unit factory pre-charge (kg) |
1 |
1.5 |
|
|
Noise level (dB) |
Indoor unit |
56.5 |
60 |
|
|
Outdoor unit |
57 |
61 |
|
|
Dimensions (mm) |
Indoor unit(W*D*H) |
500*500*1740 |
700*500*1740 |
|
|
Outdoor unit(W*D*H) |
850*400*730 |
1200*400*730 |
|
|
Weight (kg) |
Indoor unit |
130 |
170 |
|
|
Outdoor unit |
59.5 |
61 |
|
|
Recommended pipe size (mm) |
Air pipe |
12.7(Coil pipe) |
16(Coil pipe) |
|
|
Liquid pipe |
9.52(Coil pipe) |
9.52(Coil pipe) |
|
|
Water inlet pipe (constant temperature and humidity) |
G1/2" |
Drain pipe |
IDΦ19mm |
IDΦ22mm |
Allowable pipe length (m) |
Equivalent length of internal and external machine pipes |
<20 (If the project exceeds the requirements, contact the local pre-sales engineer) |
Difference in installation position of internal and external machine |
Outdoor unit higher than indoor unit: ≤10 (If the project exceeds the requirements, contact the local pre-sales engineer) |
Outdoor unit lower than indoor unit: ≤5 (If the project exceeds the requirements, contact the local pre-sales engineer) |
Design and use conditions |
Indoor ambient temperature 24ºC/wet bulb temperature 17ºC; outdoor ambient temperature 35ºC |
Standard (functional) parts |
Sight glass, high/low pressure protection switch, high pressure sensor, filter pressure differential switch |
Optional (functional) parts |
1. Extension components (configured for single-way pipelines with a length exceeding 20 meters, an oil storage bend needs to be added every 5 to 7.5 meters), with a maximum extension of 30 meters; 2. Low-temperature components (configured for areas with outdoor temperatures below -15°C), which can reach -35°C after configuration. |
Product features |
1. 4.3-inch touch screen; 2. Power-off memory, automatic start-up when receiving a call; 3. Group control networking (up to 32 units); 4. Intelligent protection: power phase loss, over-voltage, under-voltage, reverse phase protection alarm, compressor high and low pressure protection alarm, room environment high/low temperature alarm; 5. Monitor and display the operating status of the outdoor unit: condensing pressure, fan speed, etc.; 6. 500 historical records can be stored. |