Rated power |
25KVA |
300 kVA 400KVA 500KVA |
Input |
Rated input voltage (V) |
380/400/415,3Ph+N+PE |
Input voltage range (V) |
228~476,-20%~+25%full load operation,-20%~-40%derating to 70%rated load |
Rated operating frequency(Hz) |
50/60 |
nput frequency range(Hz) |
40~70 |
Bypass voltage range(%) |
Upper limit:+10,+15 or+20,default value:+15 Lower limit:
-10,-20,-30,-40,default value:-20 |
Bypass frequency range (%) |
±10 |
Input power factor |
>0.99 |
Enter THDi |
<3%(100%non-linear load) |
Battery |
|
Rated battery bus voltage (VDC) |
480 |
Supported battery types |
Lithium-ion batteries,lead-acid valve-regulated batteries |
Output |
|
Rated output voltage(V) |
380/400/415,3Ph+N+PE |
Rated output frequency(Hz |
50/60 |
Output power factor |
1 |
Inverter overload capability |
105%continuous;110%for60min; 125%for 10min; 150%for lmin; |
Efficiency |
|
Double conversion mode |
Up to 97.5% |
Dynamic online mode |
Up to 99% |
Size |
|
Size(W*D*Hmm) |
600*1000*2000 |
600*1000*2000 |
Working environmen |
|
Noise dB(A)at lm |
68 |
Altitude |
No derating for 1500 m,derating required for 1500-3000 m,and 1%derating for every 100 m increase in altitude |
IP protection leve |
IP20 |
Standards compliant |
Safety regulations:IEC 62040-1,electromagnetic compatibility:ICE 62040-2
design and testing:IEC62040-3 |
Highlight
Highly efficient and energy-saving, with efficiency up to 97.5%
Dynamic online mode efficiency is as high as 99%, input power factor >0.99
The output power factor is 1, and there is no derating from 0.5 lag to 0.5 lead.
Ultra-high power density, the 600 kW host occupies only 0.6m2, preferred in the industry.
Compatible with various lead-acid and lithium battery energy storage solutions, supports lithium battery full communication solution, and adopts battery neutral line design.
Continuous operation at 40ºC without derating, 80% rated power can still be output at 50ºC ambient temperature.
Adopts strictly screened AC and DC capacitors, special heat dissipation and ripple control design, and has a full load operating life of 15 years.
Industrial-grade internal design:independent air duct, PCB fully coated with three-proof paint and insulating glue to enhance protection, dust-proof and anti-corrosion.
Built-in synchronous dual bus function.
Supports intelligent parallel and hibernation functions, and the system capacity can reach 2MW.
9-inch LCD touch screen display with fault recording function.
Application scenarios
Government and enterprise data centers
COLO and cloud computing data center
Intelligent Manufacturing
Operator IDC
Laboratory and testing facilities
Application:
Application fields such as small and medium-sized data centers, computer rooms of small and medium-sized enterprises, intelligent manufacturing,
communication network management centers, etc. in various industries such as government, education, and medical care
Highlights :
Double conversion efficiency up to 96.5%
The output power factor is 1 (0~40ºC)
Support parallel ECO and intelligent parallel sleep
Supports built-in battery pack
Support built-in output isolation transformer
Key device life detection and early warning
Intelligent maintenance wizard service
Flexible deployment, free entry and exit
High reliability:
Dusty environments are an important cause of mid-power UPS failures. Vertiv™ Liebert® EXS 30-80kVA adopts an independent air duct design to
provide better physical and electromagnetic protection for key components, eliminating short circuits and pulls caused by dust from the source. arc
problem and passed 5 rounds of rigorous wet and dust tests
The international authoritative ISTA transportation certification enables UPS to adapt to various complex transportation conditions at home and abroad.
The output power factor is 1, and no derating is required for long-term full-load operation at 0 to 40°C, providing an enhanced solution for non-air conditioned environments and frequent heavy-load/overload operation situations.
Easy to operate and maintain:
Online detection and alarm of the life of wearing parts (fans, electrolytic capacitors) to facilitate timely maintenance and elimination of hidden faults
The humanized local display interface provides intelligent maintenance wizard services to make up for the lack of professional knowledge and avoid human error.
Medium power UPS faults are characterized by many types, scattered nodes, and complex positioning. The modular design of the core power unit helps to quickly recover from on-site faults and ensure the stability and continuity of key services.
Comes with movable casters to facilitate rapid movement of the whole machine, away from the fault site and maintenance
Free access to and from the line, flexibly adapting to various key scenarios
1. May I take some samples to test before I placing the order?
Yes, we can offer sample testing for you to verify product quality and performance.
2. What is the warranty?
We support 1 years warranty.