| Customization: | Available |
|---|---|
| Phase: | Single/Three Phases |
| Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical specifications
| General | ||
| UPS output power rating | Eaton 91PS Eaton 93PS |
8-30kW 8-40kW |
| Efficiency in double conversion mode | 96% | |
| Efficiency in Energy Saver System (ESS) mode | 99% | |
| Paralleling capability | up to 4 units | |
| Audible noise | 10kW frame 15-40kW frame |
<54 dBA in double conversion <60 dBA in double conversion |
| Altitude (max) | 1000m without derating(max 2000m) | |
| Input | ||
| Input wiring | Eaton 91PS(1:1) Eaton 91PS (3:1) & 93PS (3:3) |
1 phase+N+PE 3 phase+N+PE |
| Nominal voltage rating | Eaton 91PS (1:1) Eaton 91PS (3:1) & 93PS (3:3) |
220V;230V;240V;50/60 Hz 220/380 V;230/400 V;240/415 V;50/60 Hz |
| Input frequency range | 40 to 72 Hz | |
| Input power factor | 0.99 | |
| Input iTHD | 8-10kW 15-40kW |
<5% <4% |
| Soft start capability | Yes | |
| Internal backfeed protection | Yes | |
| Output | ||
| Output wiring | Eaton 91PS(1:1 &3:1) Eaton 93PS (3:3) |
1 phase+N+ PE 3 phases+N+PE |
| Nominal voltage rating |
Eaton 91PS(1:1 &3:1) Eaton 93PS (3:3) |
220 V;230 V;240 V 50/60 Hz 220/380 V;230/400 V;240/415V |
| Load power factor range | 0.8 lagging-0.8 leading | |
| Battery | ||
| Battery type | VRLA | |
| Charging mode | Advanced Battery Management(ABM) or Float | |
| Temperature compensated charging | Option | |
| Battery quantity | Internal External |
32 blocks, 192 cells per battery string 28-40 blocks per string |
| Charge current limit | 10kW frame 15/20 kW frame 30/40 kW frame |
Configurable, maximum 12.5A Configurable, maximum 18/25A Configurable, maximum 36/50A |
| Battery start capability | Yes | |
| Altermative backup power sources | Li-lon batteries Super capacitors Wet cell batteries NiCd batteries |
|
| Options and accessories | ||
| Long life batteries | ||
| External battery cabinets and supercapacitor cabinets | ||
| External maintenance bypass switches | ||
| Battery breaker enclosures for rack batteries | ||
| Connectivity | ||
| Native relay inputs/outputs |
5 relay inputs and dedicated EPO I relay output More relay contacts available as option |
|
| Software | Eaton Intelligent Power Manager Eaton Intelligent Power Protector |
|
| Gigabit Network card (NETWORK-M2) |
Web/SNMP Third party certified cybersecurity Up to 3 optional sensors(EMPDT1H1C2): Temperature, humidity and two status inputs |
|
| Industrial Gateway card (IND GW-M2) |
Web/SNMP/Modbus RTU and TCP Third party certified cybersecurity Up to 3 optional sensors(EMPDT 1H1C2): Temperature, humidity and two status inputs |
|
| Power Xpert UPS Minislot card (PXGMSUPS) |
Web/SNMP/Modbus RTU and TCP/BACnet IP Optional Sensor (EMP001): Temperature, humidity and two status inputs |
|
| Industrial Relay-MS card (INDRELAY-MS) |
5 relay outputs/ 1 relay input | |
| Compliance with standards | ||
| Safety | IEC 62040-1; CB certified | |
| EMC | IEC 62040-2 | |
| Performance | IEC 62040-3 | |
| RoHS | EU directive 2011/65/EU | |
| WEEE | EU directive 2012/19/EU | |