Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Symmetra PX 48 kW |
Input | |
Gnd system | 3P+N+G |
Voltage range | 340-477V@full load |
Frequency | 50 Hz |
Frequency range | 40-70 Hz with 10 Hz/s slew rate |
Power factor (PF) | 0.99@load>25%,>0.95@load>15%,>0.90@load>10% |
THDi (full load) | <5% |
Nominal input current | 77A@380V,73A @400V,70A @415V |
Maximum input current | 84.4A @380V,80.2A@400V,77.3A@415V |
Input current limit | 98.3 A@380 V/400V/415V |
Maximum input short-circuit level | 30 kA |
Output | |
Power raling | 48 kW |
Grid system | 3P+N+G |
Voltage (nominal) | 380/400/415V L-L |
Nominal output current | 73A@380V,69A@400V,67A@415V |
Frequency | 50/60 Hz bypass synchronized,50/60 Hz +1-0.1%free running |
Synchronized slew rate | Programmable to 0.25,0.5,1,2,4,6 Hz/s |
Overload (normal and battery operation) | 150% for 60 seconds,125%for 10 min,100%continuous |
V thd | <2%from 0 to 100% linear load,<5% full nonlinear load according to IEC/EN 62040-3 |
Load PF | From 0.5 leading to 0.5 lagging without any derating |
Bypass | |
V nomina | 380V/400 V/415V |
Voltage (range) | +/-10%from selected voltage |
Frequency (nominal) | 50/60 Hz |
Frequency (range) | +/-0.1 Hz,+1-3 Hz,+/-10 Hz(user selectable) |
Nominal input current | 73A@380V,69A@400V,67 A@415V |
Eficleng] | |
AC-AC at nominal mains | 295%at 35%-100%load;≥90%@15%-34%load |
DC-AC at nominal baltery voltage | ≥94%at 25%-100%load;≥90%@15%-24%load |
Mechanical | |
Dimensions (HxWxD) | 1,991x600x1,070 mm |
Weight | 796 kg |
Environmental | |
Storage temperature,UPS,and batteries | -15 to 40ºC with batteries,approximately 6-8 months 25 ºC battery self-discharge, 1-2 B16months@45ºC |
Operating temperature* | 0 to 40ºC(32 to 104F) |
Regulatory compliance | |
Symmetra PX | Symmetra PX 160 kW | |
Input | ||
system | 3P+N+G | |
Voltage range | 340-477 V@full load | |
Freguency | 50 Hz | |
Frequency range | 40-70 Hz with 10 Hz/s slew rate | |
Power factor (PF) | >0.98 at load >50% | |
THDi (full load) | <5% | |
Nominal input current | 154A@380V,146A@400V,141A@415V | 256A@380V,243 A@400V,234A@415V |
Maximum input current | nput current is based on nominal voltage,rated load,and full battery charge current 169A@380 V;160 A @400V;155A@415 V |
Input current is based on nominal woltage,rated load,and full battery charge current 281A@380 V,267 A 400V,258A@415V |
Maximum input short-circuit level | 30 kA | |
Output | ||
Power rating | 96 kW | 160 kW |
Grid system | 3P+N+G | |
Voltage (nominal) | 380 V/400 V/415 V | |
Nominal output current | 147A@380V,139A@400V,134A@415V | 243A@380V,231A@400V,223A@415V |
Frequency | 50/60 Hz bypass synchronized,50V60 Hz+/-0.1%free running | |
Synchronized slew rate | Programmable to 0.25,0.5,1,2,4,6 Hz/s | |
Overload (normal and battery operation) | Normal:150%for 60 seconds,125%for 10 min,100%continuous Battery:150%for 60 seconds,125%for 10 minutes |
|
V thd | <2%from 0 to 100%linear load,<5%full nonlinear load according to IEC/EN 62040-3 | |
Load PF | From 0.5 leading to 0.5 lagging without any derating | |
Bypass | ||
V nominal | 380 V/400 V/415 V | |
Voltage (range) | +/-10%(from selected voltage) | |
Frequency (nominal) | 40-70 Hz | |
Frequency (range) | +/-0.1 Hz,+/-3 Hz,+/-10 Hz(user selectable) | |
Nominal input current | 147A@380V,139A@400V,134A@415V | 243A@380V,231A@400V,223A@415V |
Efflcigne | ||
AC-AC at nominal mains | 95%at 35%-100%load,≥90%@15%-34%load | |
DC-AC at nominal baltery voltage | ≥94%at 25%-100%load,≥90%@15%-24%load | |
Mechanical (UPS with 3-in-1 modular power distribution,bypass,and battery cabinet) | ||
Dimensions (HxWxD) | 1,991x1,200x1,080 mm | 1,991x1,800x1,080 mm |
Weight | 1.814 kg | 2,878 kg |
Environmental | ||
Storage temperature, UPS, and batteries Storage temperature,UPS,and batteries |
15 to 40 with batteries,approximately 6-8 months 25 C battery self-discharge, 1-2 months @45 ºC |
|
Operating temperature* | 0to 40ºC(32 to 104 F) | |
Full load loss at nominal mains (BTU) | 17,244 BTLWhr | 28,741 BTU/hr |
Regulatory compliance | ||
CE, EN/IEC 62040-1-1, EN/IEC/UL 60950-1, EN 50091-2/IEC 62040-2 (class A), FCC15A, EN/IEC 62040-3 | ||