Phase: | Three Phase |
---|---|
Type: | On-line |
Protection: | Unbalanced Loads |
Application: | Industry |
Classification: | Lighting/Power |
Standby Time: | Long-acting Machine |
Customization: |
---|
Suppliers with verified business licenses
Rated power | 300 kVA | 600 kVA |
Input | ||
Rated input voltage(V) | 380/400/415,3Ph+N+PE | |
Input voltage range(V) | 228~476,-20%~+25% full load operation,-20%~-40% derating to70% rated load | |
Rated operating frequency(Hz) | 50/60 | |
Input frequency range(Hz) | 40~70 | |
Bypass voltage range(%) | Upper limit:+10,+15 or +20, default value:+15 Lower limit: -10,-20,-30, -40, default value:-20 | |
Bypass frequency range(%) | ±10 | |
Input power factor | >0.99 | |
Enter THDi | <3%(100% non-linear load) | |
Battery | ||
Rated battery bus voltage(VDC) | 360-600 | |
Supported battery types | Lithium-ion batteries, lead-acid valve-regulated batteries | |
Output | ||
Rated output voltage (V) | 380/400/415,3Ph+N+PE | |
Rated output frequency(Hz) | 50/60 | |
Output power factor | 1 | |
Inverter overload capability | ≤105% continuous;≤110% for 60min;≤125% for 10min;≤150% for 1min; | |
Efficiency | ||
Double conversion mode | Up to 97.5% | |
Dynamic online mode | Up to 99% | |
Size | ||
Size(W*D*H mm) | 600*1000*2000 | |
Working environment | ||
Noise dB(A) at 1m | 70 | |
Altitude | No derating for 1500 m, derating required for 1500-3000 m, and 1% derating for every 100m increase in altitude. | |
IP protection level | IP20 | |
Standards compliant | Safety regulations: IEC 62040-1, electromagnetic compatibility: ICE 62040-2,design and testing: IEC62040-3 |