| Customization: | Available |
|---|---|
| Phase: | Three Phase |
| Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ARRAY 3A3 PT UPS Technical Specifications
| Power modules | |
| Power offering(kW) | 60kW(62.5kW optional) |
| Frame options | |
| 600kW | Standard offer input/output/MBS /bypass switches |
| General characteristics | |
| Efficiency in Energy Saver System (ESS) | Up to 99% |
| Efficiency in double-conversion mode | Upto 97% |
| Parallel capability | Standard 4 units external parallel(Max 8 units with factory customization) |
| Cold start | Supported |
| Softstart | Rectifier ramp up. compatible with generator. ramp up rate configurable |
| Input characteristics | |
| Voltage | 380/400/415V |
| Voltage range | 301~478V L-L 175~276V L-N |
| Frequency range | 50/60 Hz |
| Power factor | >0.99 |
| Input current distortion | <3%@100% load capacity |
| Battery | |
| Battery Type | Lithium, VRLA |
| Charging method | ABM |
| Battery Voltage | 432-528Vdc(Selectable) |
| Battery Connection | Two wire(no neutral) |
| Output | |
| Voltage | 380/400/415V 4 wire |
| Frequency range | 50/60 Hz |
| Regulation | ±1% steady state |
| Voltage THD | <1%(100% linear load) <5% (non-linear load) |
| Overload | 125% 10 mins |
| Compliance with standards | |
| Safety | IEC 62040-1 |
| EMC | IEC 62040-2 |
| Performance | IEC 62040-3 |
| RoHS | EU directive 2011/65/EU |
| UPS dimensions (mm) | Power Rating (W) | Module * Qty | ||||
| 3A3 PT 300kVA Frame with MBS (Height* Depth* Width) |
2000*1100*600 | 3A3 PT-120 | 60kW*2 | |||
| 3A3 PT-125 | 62.5kW*2 | |||||
| 3A3 PT 600kVA Frame with MBS (Height* Depth* Width) |
2069*1100*1200 | 3A3 PT-180 | 60kW*3 | |||
| 3A3 PT-187 | 62.5kW*3 | |||||
| UPM dimensions (mm) | 3A3 PT-240 | 60kW*4 | ||||
| Height | 173.4 (4U) | 3A3 PT-250 | 62.5kW*4 | |||
| Depth | 700 | 3A3 PT-300 | 60kW*5 | |||
| Width | 439 | 3A3 PT-312 | 62.5kW*5 | |||
| Weight (kg) | 3A3 PT-360 | 60kW*6 | ||||
| 300kVA UPS (w/o UPM) | 375 | 3A3 PT-375 | 62.5kW*6 | |||
| 600kVA UPS (w/o UPM) | 726 | 3A3 PT-420 | 60kW*7 | |||
| UPM | 39 | 3A3 PT-437 | 62.5kW*7 | |||
| 3A3 PT-480 | 60kW*8 | |||||
| 3A3 PT-500 | 62.5kW*8 | |||||
| 3A3 PT-540 | 60kW*9 | |||||
| 3A3 PT-600 | 60kW*10 | |||||