Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated Power (kVA/kW)* | 250 kVA/250 kW | 300 kVA/300 kW | 400 kVA/400 kW | 500 kVA/500 kW | 600 kVA/600 kW |
Input | |||||
nput voltage (V) | 380/400/415V(3-phase +Neutral +PE) | ||||
Frequency (Hz) | 40-70 Hz | ||||
nput power factor | >0.99 | ||||
THD | <3% | ||||
Input voltage range | 323-477V | ||||
Dual mains inpu | Yes (default:single mains input) | ||||
Outpu | |||||
Parallel | Up to 5 UPSs for capacity (or 5+1 for redundancy) | ||||
Nominal output voltage (V) | 380/400/415V | ||||
Efficiency:Double conversion mode | Up to 96% | ||||
ECO mode | 99% | ||||
Overload capacity in normal operation | 150%for 1 minute,125%for 10 minutes,105%continuous | ||||
Output voltage tolerance | +/-1% | ||||
Load Power Factor compatibility | From 0.5 leading to 0.5 lagging | ||||
Communication and management | |||||
Communication interface | RS485,dry contacts,Ethernet (SNMP,Modbus,TCP/IP,BACnet) | ||||
Control panel | 7-inch touchscreen LCD,status,and display console | ||||
Weights and dimensions | |||||
UPS,unpackaged/dimensions (H × W × D) | 1970x600x850mm | 1970x1000x850 mm | |||
UPS,unpackaged weight | 425 kg | 465 kg 560 kg | 640kg | 720 k | |
Raalatop, | |||||
Safety | EC/EN 62040-1 | ||||
EMC | EC/EN 62040-2 | ||||
Performance | EC/EN 62040-3 | ||||
Markin | CE | ||||
Raitery tyee | |||||
Battery type | VRLA | ||||
Number of batteries | 36-50 | ||||
Charging power in %of output power (selectable) |
26% | 24% | |||
Environmental | |||||
Relative humidity | 0 to 95%non-condensing | ||||
Operating elevation | 0 to 1500 m without derating | ||||
Audible noise at 1m from unit | 70db | 72db | |||
Protection class | IP20 (IP31 with optional kit) | ||||