| Customization: | Available |
|---|---|
| Phase: | Three Phase |
| Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
3C3 HD 400-600K Technical Data
| Model | 3C3 HD-400K | 3C3 HD-500K | 3C3 HD-600K | ||
| Power rating | 400KVA/400KW | 500KVA/500KW | 600KVA/600KW | ||
| Input | Wiring | Three phase+Neutral+Ground | |||
| Frequency | 50/60Hz | ||||
| Frequency range | 40-72Hz | ||||
| Power factor | ≥ 0.99 | ||||
| Input voltage range | 240 ~ 478Vac / 138 ~ 276Vac | ||||
| Bypass voltage range | 340 ~ 438Vac / 196 ~ 253Vac | ||||
| THDI | <3% @ full linear load | ||||
| Output | Voltage | 230/400Vac(220/380,240/415 optional) | |||
| Power factor | 1 | ||||
| Freqency | 50Hz / 60Hz | ||||
| THDV | <1% @ full linear load | ||||
| Over load | 10mins@111-125% ,1min@126-150% | ||||
| Parallel | 4 units | ||||
| Efficiency | Double conversion mode | Up to 97% | |||
| ESS mode | Up to 99% | ||||
| Battery | Battery type | VRLA,NiCad,Lithium battery | |||
| Battery voltage | 480V(40 pcs)~690V (50 pcs), default 480V | ||||
| Charge current( max ) | 280A | 320A | 400A | ||
| Environment | Ambient temperature | 0-40°C | |||
| Storage temperature | -15 ~ +55°C | ||||
| Ambient humidity | 5 - 95 % | ||||
| Altitude | No derating < 1000m | ||||
| Dimension | W*D*H( mm ) | 1100*1000*2000 | |||
| Weight | Net weight | 650kg | 700kg | 820kg | |
| Gross weight | 770kg | 820kg | 940kg | ||
| Standard | Safty | IEC/62040 | |||