Eaton 93PR UPS 25-200 kW | ||
Technical specifications | ||
General | ||
UPS output power rating(1.0 p.f.) | 25,50,75,100,125,150,175,200kW | |
Efficiency in double conversion mode | >96% | |
Efficiency in Energy Saver System (ESS) | >99% | |
Static bypass rating | 200kW | |
External paralleling | up to 4 units with HotSync technology | |
UPS topology | Double conversion | |
UPS degree of protection | IP20 | |
Acoustic noise at 1 m,in 25ºC ambient temperature | <70 dBA in double conversion,<55 dBA in ESS | |
Altitude (max) | 1000m above sea level at 40ºC.Maximum 2000m with 1%derating per each add.100 m | |
Input | ||
Rated input voltage | 220/380 V,230/400 V,240/415V50/60 Hz | |
Voltage tolerance -Rectifier input | 187 to 276 V | |
Voltage tolerance -Bypass input | rated voltage -15%/+10% | |
Rated input frequency | 50 or 60 Hz,user configurable | |
Frequency tolerance | 40 to 72 Hz | |
Input wiring | 3 phase+neutral | |
Input power factor at 100%load | >0.99 | |
Input ITHD | <3% | |
Rated input r.m.s current | 25kW 50kW 75kW 100kW 125kW 150kW 175kW 200kW | |
380V | 40 A 80 A 120 A 159 A 199 A 239 A 278 A 318 A | |
400V | 38 A 76 A 114 A 151 A 189 A 227 A 264 A 302 A | |
415V | 37 A 73 A 110 A 146 A 182 A 219 A 255 A 291 A | |
Soft start capability | Yes | |
Internal backfeed protection | Yes | |
Output | ||
Output wiring | 3 phase+neutral | |
Rated output voltage rating | 220/380 V,230/400 V,240/415 V,configurable | |
Total voltage harmonic distortion | <1%(100%linear load);<3%(100%non-linear load) | |
Output power factor | 1.0 | |
Permitted load power factor | 0.8 lagging to 0.8 leading | |
Overload on inverter | 10 min 102-110%,60 sec 111-125%,10 sec 126-150%,300 ms>150%. | |
Overload on bypass | Continuous<125%,20 ms 1000% | |
Battery | ||
Battery type | 12V,VRLA | |
Charging method | ABM technology or Float | |
Temperature compensation | Optional | |
Battery nominal voltage(VRLA) | 480 V | |
Battery quantity | 36 to 44 blocks.Default is 40 blocks | |
Charge current limit | Default 5A,configurable maximum 25A per UPM | |
Battery start capability | Yes | |
Communications | ||
Minislot | 3 communication bays | |
Network/SNMP interface | Yes,optional | |
Serial ports | Built-in host and device USB | |
Standard connectivity ports | Mini-slot ports for optional cards,Device USB and Host USB,RS-232 service port,relay output, 5 building alarm inputs and a dedicated EPO |
|
Accessories | ||
MiniSlot connectivity (Web/SNMP,ModBus/Jbus,Relay) | ||
External Battery Cabinet(EBC) | ||
Parallel Tie Cabinet(PTC) | ||
External Maintenance Bypass Switches(EMBS) | ||
External Battery Cabinet Breaker(EBCB) | ||
Compliance with standards | ||
Safety | IEC 62040-1 | |
EMC | IEC 62040-2 | |
Performance | IEC 62040-3 | |
Due to continuous product improvement programmes,specifications are subject to change without notice. |