Technical specifications² | ||||
UPS rating (unity power factor 1.0) | ||||
kVA | 200 250 275 300 400 500 550 600 675 750 825 900 1000 1100 1200 | |||
kW | 200 250 275 300 400 500 550 600 675 750 825 900 1000 1100 1200 | |||
General characteristics | ||||
Efficiency | 99% with Energy Saver System (Up to 97%(480V) and 96%(600V and 400V) in double-conversion) |
|||
Parallel capability | 4 UPS units maximum for distributed bypass and 8 UPS units maximum with SBM | |||
Max modules per size | Up to 2 modules 300 kW Up to 3 modules 600 kW Up to 4 modules 900/1200 kW |
|||
Audible noise | As low as 75 dBA @ 1meter* | |||
Altitude(max) | 1000m at 40 degree C(104 degree F) 1000m at 35 degree C(95 degree F) when UPM capacity is above 275 kW |
|||
N+1 redundancy capable | Yes | |||
Field upgradeable | Yes | |||
System bypass module | Included | |||
Input characteristics | ||||
Voltage | 480V standard 600/575V and 400/415V optional | |||
Voltage range | +10%/-15% | |||
Frequency range | 45-65 Hz | |||
Power factor | 0.99(minimum) | |||
Input current distortion | <3%(no input filter required) | |||
Soft start capability | Yes | |||
Internal backfeed protection | Yes | |||
Output characteristics | ||||
Voltage | 480V standard; 600/575V and 400/415V optional | |||
Regulation | ±1% | |||
Inverter | PWM with IGBT switching | |||
Voltage THD | <2%(100% linear load); <5%(non-linear load) | |||
Load power factor range | Up to a 9 power factor leading without derating | |||
Overload | 110% for 10 minutes, 125% for 2 minutes, 150% for 15 seconds | |||
Battery | ||||
Battery types | VRLA,AGM,wet cell,lithium-ion | |||
Battery voltage | 480V | |||
Temperature compensation | Optional | |||
Charging method | ABM technology or float, selectable |
Dimensions and weights(480V and 400V** system) | 480V | 400V | |
200,250,275,300 kW | 52.5"w×34.4"d × 74"h | 2,150 lb (975 kg) | 1,886 lb(857 kg) |
200-300 kW+1 redundant | 73.8"w×34.4"d × 74"h | 3,184 lb (1,447 kg) | NA |
Field upgrade module,300kW | 29"w×34.4"d × 74"h | 1,037 lb (470 kg) | 1,047 lb(475 kg) |
400,500,550,600 kW | 73.8"w×34.4"d × 74"h | 3,184 lb (1,447 kg) | NA |
400-600 kW+1 redundant | 103"w×34.4"d × 74"h | 4,221 lb (1,918 kg) | NA |
675, 750, 825, 900kW | 141"w×34.4"d × 74"h | 5,236 lb (2,375 kg) | 5,236 lb(2,375 kg) |
675,750,825,900kW+1 redundant | 170.1"w×34.4"d × 74"h | 6,523 lb (2,959 kg) | NA |
1000,1100,1200 kW | 170.1"w×34.4"d × 74"h | 6,523 lb (2,959 kg) | 6,620 lb(3,003 kg) |
Dimensions and weights (575V and 600V** system) | ||
200,225,250,275 kW/kVA | 102.9"w × 34.4" d × 74"h | 4,354 lb (1975 kg) |
200-275 kW/kVA+1 redundent | 126.2"w × 34.4" d × 74"h | 5,683 lb (2578 kg) |
300 kW/kVA | 126.2"w × 34.4" d × 74"h | 5,683 lb (2578 kg) |
400,450,500,550 kW/kVA | 126.2"w × 34.4" d × 74"h | 5,683 lb (2578 kg) |
400-550 kW/kVA+1 redundent | 155.2"w × 34.4" d × 74"h | 6,722 lb (3049 kg) |
675,750,825 kW/kVA | 155.2"w × 34.4" d × 74"h | 6,722 lb (3049 kg) |
675, 750, 825 kW/kVA +1 redundent |
195"w × 34.4" d × 74"h | 10,050 lb (4559 kg) |
1000, 1100 kW/kVA | 224"w × 34.4" d × 74"h | 11,550 lb (5239 kg) |
Field upgrade module, 275 kW | 29"w × 34.4" d × 74"h | 1037 lb (470 kg) |
Control panel(LCD) | Color touchscreen |
Battery startup | Standard |
Frequency conversion | Standard |
Multi-language | Standard |
Building alarm inputs | 5(galvanic isolated) |
External maintenance bypass |
PDU, RPP, and STS |
Maintenance bypass module, matching cabinet, 2/3/4 breaker |
Human Machine Interface(HMI) design for monitoring of connected equipment |
DC disconnects |
100 kAIC input breakers |
Safety | UL1778, cUL |
EMC | IEC 62040-2,C3 limits |
PredictPulse is the industry's first cloud-based 24×7 remote monitoring and predictive analytics subscription service to forecast data center power component failure and proactively replace components before failure. PredictPulse is included with the 9395P High Performance UPS for the first year at no-charge along with a PXGX-UPS card and Environmental Monitoring Probe (customer self-installs via outbound email server or optional 4G/LTE wireless modem). |
Software compatibility: Power Xpert |
Communications cards: Four communication bays standard. The following connectivity options can be installed at any time: - PXGX-UPS card (included with PredictPulse activation) - ModBus RTU card - AS/400 Relay card - Industrial Relay card - HotSync CAN Bridge card - Environmental Monitoring Probe (included) - BACnet IP communication protocol supported |
Remote inputs/outputs: Five building alarm inputs and one summary alarm contact (5A @ 120V) standard |
Remote monitor panel: Eight backlit status indicator lamps plus an audible horn |