Model |
UL33 |
Power |
20KVA |
30KVA |
40KVA |
60KVA |
80KVA |
100KVA |
Parameters |
W×D×H(mm) |
600×860×1400 |
800×860×1800 |
900×850×1900 |
Weight(kg) |
440 |
528 |
654 |
811 |
790 |
790 |
Input characteristics (rectifier) |
|
|
|
Input voltage |
380VAC,Three-phase three-wire |
Rated operating frequency |
50/60Hz |
Input voltage range |
208V~437V, -20%~+15% full load, -25%~-45% linear derating, -45% can carry 50% load |
Input frequency range |
50Hz±10% |
Input power factor |
Fully loaded>0.99 |
Input power slow start function |
1-255s can be set, default is 10s |
Rectifier output characteristics |
|
|
|
Output voltage regulation accuracy |
0.5% |
DC ripple low voltage |
≤1% |
Output characteristics (inverter) |
|
|
|
Inverter output voltage |
380, three-phase four-wire |
Output power factor |
0.8 |
Voltage stability |
Steady state |
<±1% typical value |
Transient |
<±5% typical value |
Steady state response time |
<20ms |
Inverter overload capability |
105%~125% 10 minutes, 125%~150% 1 minute, >150% 200 milliseconds |
Phase shift characteristics |
|
<0.5° |
|
<0.5° |
Total harmonic content THDv |
|
<1% (typical value) |
|
<3% (typical value) |
Bypass |
|
|
|
Bypass input voltage |
380/400/415VAC, Three-phase four-wire |
Bypass voltage range |
Default -20% ~ +15%, -40%, -30%, -10% ~ +10%, +15% and other range values can be set through software |
Bypass overload capability |
≤135% long-term operation, 1000%20ms |
System |
|
|
|
Frequency |
50Hz(can be set) |
Synchronization tracking range |
±0.5Hz~3Hz adjustable every 0.5Hz |
Measured frequency accuracy |
50Hz/60Hz±0.02% |
System efficiency (full load) |
Up to 93% |
Working environment |
|
|
|
Operating temperature range |
0~40ºC |
Storage temperature |
-25~70ºC(excluding battery) |
Relative humidity |
0~95% no condensation |
Maximum operating height |
≤Altitude 1500m,for every 100m above 1500m, the load will be reduced by 1% |
Noise(1m) |
55dB |
70dB |
Protection level |
IP20 |
Standards |
Safety regulations: IEC62040-1-1,electromagnetic compatibility: IEC62040-2, design and testing: IEC61000-4 |