93HD-10~80K 33 Industrial UPS Specifications
Capacity 384Vdc |
Rated capacity | 10kVA | 15kVA | 20kVA | 30kVA | 40kVA | 50kVA | 60kVA | 80kVA | ||||||||
Active power | 9kW | 13.5kW | 18kW | 27kW | 36kW | 45kW | 54kW | 72kW | |||||||||
Mains | Rectifier topology | 6 or 12 pulses | |||||||||||||||
Mains input and bypass input | Dual input | ||||||||||||||||
Input type | Three-phase + PE | ||||||||||||||||
Rated AC input | 380/400/415VAC | ||||||||||||||||
Voltage range | 285VAC ~ 498VAC | ||||||||||||||||
Rated frequency | 50/60Hz | ||||||||||||||||
Frequency range | 45-66Hz | ||||||||||||||||
Bypass | Rated AC input | 380/400/415VAC (three-phase + neutral) | |||||||||||||||
Voltage range | -40% ~ +20% adjustable | ||||||||||||||||
Frequency range | 50/60Hz (± 2.5%, ±5%, ±10%, ±20% adjustable) | ||||||||||||||||
Output | Rated AC output | 380/400/415VAC (three-phase + neutral) | |||||||||||||||
Voltage tolerance (Static) | ±1% | ||||||||||||||||
Power factor | 0.9 | ||||||||||||||||
Voltage tolerance (Dynamic) | ±5% (variable within 0~100% load) | ||||||||||||||||
THDv | < 1%(100% linear load) | ||||||||||||||||
Voltage dynamic response | < 20ms | ||||||||||||||||
Synchronization range | ±2 Hz by default ( ±0.5~ ± 3Hz adjustable) | ||||||||||||||||
Inverter overload capacity | Continuous operating at 110% load; 10-min operating at 125% load; 1-min operating at 150% load; |
||||||||||||||||
Frequency stability | ±0.05% | ||||||||||||||||
Waveform | Pure sine wave | ||||||||||||||||
Efficiency | Double-conversion mode | Up to 92% | |||||||||||||||
ECO mode | Up to 96% | ||||||||||||||||
Parallel system | Parallel Unit | Up to 8 | |||||||||||||||
Battery configuration |
Battery quantity | VRLA battery: 30 - 32 blocks | |||||||||||||||
Dimension | Depth (mm) | 720 | 750 | ||||||||||||||
Height (mm) | 1100 | 1400 | |||||||||||||||
Width (mm) | 6-pulse | 560 | 800 | ||||||||||||||
12-pulse | 970 | 1270 | |||||||||||||||
Environmental and general parameters |
Display interface | 7-inch touch panel with LED indicator | |||||||||||||||
Communication interface | Modbus RS232/RS485 standard; Eaton industrial network card INDGW-M2 optional | ||||||||||||||||
Standard protection level | IP20, Up to IP42 optional | ||||||||||||||||
Temperature | 0 ~ 40ºC | ||||||||||||||||
Humidity | 0 ~ 95% (non-condensing) | ||||||||||||||||
Noise | ≤57dB | ≤60dB | ≤63dB | ||||||||||||||
Compliance | Safety | IEC60950-1,IEC62040-1-1 | |||||||||||||||
Electromagnetic compatibility | IEC62040-2,IEC62040-3 | ||||||||||||||||
Certification | CE/YDT1095-2018 |
Capacity 384Vdc |
Rated capacity | 100kVA | 120kVA | 160kVA | 200kVA | |
Active power | 90kW | 108kW | 144kW | 180kW | ||
Mains | Rectifier topology | 6 or 12 pulses | ||||
Mains input and bypass input | Dual input | |||||
Input type | Three-phase + PE | |||||
Rated AC input | 380/400/415VAC | |||||
Voltage range | 285VAC ~ 498VAC | |||||
Rated frequency | 50/60Hz | |||||
Frequency range | 45-66Hz | |||||
Bypass | Rated AC input | 380/400/415VAC (three-phase + neutral) | ||||
Voltage range | -40% ~ +20% adjustable | |||||
Frequency range | 50/60Hz (± 2.5%,±5%,±10%,±20% adjustable) | |||||
Output | Rated AC output | 380/400/415VAC (three-phase + neutral) | ||||
Voltage tolerance (Static) | ±1% | |||||
Power factor | 0.9 | |||||
Voltage tolerance (Dynamic) | ±5%(variable within 0 ~ 100% load) | |||||
THDv | < 1%(100% linear load) | |||||
Voltage dynamic response | < 20ms | |||||
Synchronization range | ±2 Hz by default ( ±0.5 ~ ± 3Hz adjustable) | |||||
Inverter overload capacity | Continuous operating at 110% load; 10-min operating at 125% load; 1-min operating at 150% load; |
|||||
Frequency stability | ±0.05% | |||||
Waveform | Pure sine wave | |||||
Efficiency | Double-conversion mode | Up to 92% | ||||
ECO mode | Up to 96% | |||||
Parallel system | Parallel Unit | Up to 8 | ||||
Battery configuration |
Battery quantity | VRLA battery: 30 - 34 blocks | ||||
Dimension | Depth (mm) | 855 | ||||
Height (mm) | 1900 | |||||
Width (mm) | 6-pulse | 890 | 1245 | |||
12-pulse | 1415 | 1770 | ||||
Environmental and general parameters |
Display interface | 7-inch touch panel with LED indicator | ||||
Communication interface | Modbus RS232/RS485 standard; Eaton industrial network card INDGW-M2 optional | |||||
Standard protection level | IP20, Up to IP42 optional | |||||
Temperature | 0 ~ 40ºC | |||||
Humidity | 0~95% (non-condensing) | |||||
Noise | ≤67dB | ≤69dB | ||||
Compliance | Safety | IEC60950-1,IEC62040-1-1 | ||||
Electromagnetic compatibility | IEC62040-2,IEC62040-3 | |||||
Certification | CE/YDT1095-2018 |