Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical Specifications | 9PX 1kVA | 9PX 1.5kVA | 9PX 2.2kVA | 9PX 3kVA | ||
Rated power(VA/W) | 1000VA/1000W | 1500VA/1500W | 2200VA/2200W | 3000VA/3000W | ||
Model | RT2U (Tower/Rack 2U) | RT2U (Tower/Rack 2U) and RT3U (Tower/Rack 3U) | ||||
Electrical characteristics | ||||||
Technology | In-line double conversion system with power factor correction (PFC). | |||||
Nominal voltage | 200/208/220/230/240V | |||||
Mains input voltage range | 176-276V without derating (up to 100-276V with derating) | |||||
Mains input frequency range | 40-70Hz, 50/60Hz auto selection, inverter mode | |||||
Efficiency | Up to 91.5% in mains mode (Up to 97.5% in high efficiency mode) |
Up to 92.5% in mains mode (Up to 97.5% in high efficiency mode) |
Up to 93.5% in mains mode (up to 98% in high efficiency mode) |
Up to 94% in mains mode (up to 98% in high efficiency mode) |
||
Connections | ||||||
Input | 1 IEC C14(10A) | 1IEC C20(16A) | ||||
Output | 8 IEC C13(10A) socket | 8 IEC C13 (10A) socket + 2 IEC C19 (16A) socket | ||||
Maintain bypass output via Hotswap | 6 IEC 10A socket | |||||
Switch socket group | 2 socket groups | |||||
Battery | ||||||
Typical backup time(min)** | 300W | 500W | 800W | 1200W | 1800W | 2500W |
9PX 1000 | 28 | 16 | 9 | |||
9PX 1000+1EBM/+4EBM | 134/530 | 79/316 | 47/188 | |||
9PX 1500 | 38 | 23 | 13 | 7 | ||
9PX 1500+1EBM/+4EBM | 143/536 | 86/319 | 52/192 | 32/120 | ||
9PX 2200 | 43 | 25 | 15 | 9 | 5 | |
9PX 2200+1EBM/+4 EBM | 206/818 | 123/491 | 74/297 | 47/189 | 29/118 | |
9PX 3000 | 60 | 36 | 22 | 13 | 7 | 4 |
9PX 3000+1EBM/+4EBM | 221/824 | 135/504 | 83/307 | 52/194 | 33/122 | 22/82 |
Battery management | ABM® & Temperature Compensated Charging Method (User Selectable), Automatic Battery Testing, Deep Discharge Protection, Automatic Identification of External Battery Packs. | |||||
Communication | ||||||
Communication port | 1 USB port + 1 serial RS232 port + 1 remote on/off terminal + 1 remote power-off terminal + 1 output dry node terminal | |||||
Communication slots | A slot is used to install a network-MS card, a Modbus-MS card, or a dry-node-MS card |