| Customization: | Available |
|---|---|
| Phase: | Three Phase |
| Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Galaxy VL | Features |
| Nominal power rating (kVA=kW) |
200.300.400.500 |
| Scalability | From 200 kW to 500 kWwith 50 kW power module increments |
| N+1 power ratings | Up to 450 KW N+ |
| Technical rating | 500 kW |
| Topology | On-line double conversion,UL-verified eCawersion |
| Key features | |
| Modular design | Power module,control module power supply unit |
| Third-party verified Live Swap |
Power odule |
| Display | 7-inch color touch display,mimic diagram on display |
| Cabinet Type | Standalone,White (RAL9003) |
| Efficiency | |
| Double conversion mode | >97% |
| eConverison mode | Up to 99% |
| ECO mode | Up to 99% |
| Input | |
| Rated voltage | 380/400/415/440/480 VAC |
| Input voltage range (phase to phase) |
331-552V |
| Single mains/dual mains | Single mains as standard.Easily converted to dual mains. |
| nput current total harmonic distortion (THDI) |
<3% |
| Input power factor | >0.99 at load >25% |
| Cable entry | Top as standard.Optionable bottom cable entry cabinet available. |
| Input backfeed protection | Input backfeed protection:Included Bypass backfeed protection:External orinternal with kit. |
| Maximum short-circuit rating | 65 kA lcw |
| Output | |
| Nominal output voltages | 380/400/415/440/480 VAC |
| Load power factor | PF=1740ºC(104°F)without derating |
| Voltage regulation | +/-1%(symmetrical load) |
| Frequency | 50V/60Hz±0.1%free running |
| Overload normal operation | 1min@150%;10 min@125% (110%continuous at 30ºC(86°F)) |
| Overload battery operation | 1min@125% |
| Output THDU on linear load |
<1% |
| Output THDU on non-linear load |
<3% |
| Output Voltage classification |
VFI-SS-111 |
| Galaxy VL | Features |
| Paralleling | |
| Parallel capabiity | Parallelable for capacity (3 MW)or redundancy (2.5 MW N+1) |
| Batteries | |
| Battery type | VRLA/Lithium-lon/NiCad |
| DC Bus/Number ofVRLA battery blocks |
480-576V(40-48 blocks) |
| Float Voltage.2.27 V/cell | 545-654V |
| Backup time | 5 minutes to 1 hour (longer runtime available*) |
| Maximum charging powe (0-40%load) |
80% |
| Maximum charging power (100%load) |
20% |
| Number of supported battery breakers |
4 |
| Breaker trip function | UV coil on the battery breaker |
| Temperature compensation | -3.3 mN/C/cell,forT>=25ºC 0mV/*C/cell,forT<25°ºC |
| Maximum short-circuit level | 30 kA |
| Battery test | ManuaVautomatic (selectable) |
| Battery runtime estimation | Yes |
| Battery deep discharge protectio |
Yes |
| Environment | |
| Operating temperature | 0.40ºCwithout rating |
| Storage temperature | 25°to 55ºC (-13-131 F) |
| Humidity | 0%to 95% |
| Elevationvaltitude | 1000m 100% load up to 3000m with derating |
| Audible noise at 100%load | 400V:69.5 dB;480V:68 dB |
| IP lvel (lnoress Protection | IP20 |
| Dust | Supports harsh environments Pollution degree 2 (IEC 62040). Air filter included. |
| Conformance coating | On PCBA |
| Dimensions | |
| 200-500KW UPS (HxWxD) | 1970x850x925 mm (77.6x33.5x36.4 in) |
| Weight | 200 kW UPS:495 kg (1091 Ib); 500 kW UPS:720 kg(1587 Ib) |
| Options and accessories | |
| Lithium-ion battery cabinet | Parallel communications kit |
| Maintenance bypass cabinet | Network management card |
| Bottom cable entry cabine | Internal backfeed kit |
| Battery breaker kit | Kirk key kit (480V)* |
| Air filter kit | 600V:480 V transformer cabinet (Canada) |
| Seismic kit | Classic battery cabinet (400 V)* |
| Common VRLA battery bank | Battery breaker box (400V) |
| Remote alarm panel | |