Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model Number | GXT5-5000IRT5UXLE | GXT5-6000IRT5UXLE | GXT5-8000IRT5UXLE | GXT5-10KIRT5UXLE | |||
Ratings (VA/W) | 5000 VA / 5000 W | 6000 VA / 6000 W | 8000 VA / 8000 W | 10,000 VA / 10,000 W | |||
Dimensions, mm (inches) | |||||||
Unit W × D × H | 430×630×217 (16.9×24.8×8.5) |
430×630×217 (16.9×24.8×8.5) |
430×630×217 (16.9×24.8×8.5) |
430×630×217 (16.9×24.8×8.5) |
|||
Weight, kg (pounds) | |||||||
Unit | 70.8 (156) | 70.8 (156) | 74.5 (164.2) | 74.5 (164.2) | |||
Input AC Parameters | |||||||
Operating Frequency Nominal | 50 or 60Hz (Factory Default is 50) |
50 or 60Hz (Factory Default is 50) |
50 or 60Hz (Factory Default is 50) |
50 or 60 Hz (factory-default is 50 Hz) |
|||
Voltage Range | 230 VAC | 230 VAC | 230 VAC | 230 VAC | |||
Input Wiring | Hardwire | Hardwire | Hardwire (common or split bypass) | Hardwire (common or split bypass) | |||
Output AC Parameters | |||||||
Output Receptacles | Hardwire 2 (C19), 6 (C13) |
Hardwire 2 (C19), 6 (C13) |
Hardwire 4 (C19), 4(C13) |
Hardwire 4 (C19), 4(C13) |
|||
Factory-default VAC Frequency |
230 VAC 50Hz or 60Hz, Nominal |
230 VAC 50Hz or 60Hz, Nominal |
230 VAC 50Hz or 60Hz, Nominal |
230 VAC 50Hz or 60Hz, Nominal |
|||
Waveform (On Battery) | Sinewave | Sinewave | Sinewave | Sinewave | |||
Utility (AC) Mode Overload |
>150% for Minimum 200mS; 125 - 150% for 60 seconds; 105-125% 5 Minutes; ≤105 % Continuous | >150% for Minimum 200mS; 125 - 150% for 60 seconds; 105-125% 5 Minutes; ≤105 % Continuous | >150% for Minimum 200mS; 125 - 150% for 60 seconds; 105-125% 5 Minutes; ≤105 % Continuous | >150% for Minimum 200mS; 125 - 150% for 60 seconds; 105-125% 5 Minutes; ≤105 % Continuous | |||
Battery | |||||||
Type | Valve-regulated, non-spillable, lead acid | Valve-regulated, non-spillable, lead acid | Valve-regulated, non-spillable, lead acid | Valve-regulated, non-spillable, lead acid | |||
Backup Time (100% Load) |
7 Minutes | 5.5 Minutes | 3.5 Minutes | 2 Minutes | |||
Backup Time (50% Load) |
18.5 Minutes | 14.5 Minutes | 9.5 Minutes | 7 Minutes | |||
+1 External Battery Cabinet (100% Load) |
19 Minutes | 14.5 Minutes | 9.5 Minutes | 7 Minutes | |||
+1 External Battery Cabinet (50% Load) |
48 Minutes | 38.5 Minutes | 26 Minutes | 19 Minutes | |||
Environmental Requirements | |||||||
Operating Temperature, °C (°F) |
0 to 40 (+32 to +104) (no derating) | 0 to 40 (+32 to +104) (no derating) | 0 to 40 (+32 to +104) (no derating) | 0 to 40 (+32 to +104) (no derating) | |||
Storage Temperature, °C (°F ) |
-15 to 50+ (5 to +122) | -15 to 50+ (5 to +122) | -15 to 50+ (5 to +122) | -15 to 50+ (5 to +122) | |||
Relative Humidity | 0% to 95%, non-condensing |
0% to 95%, non-condensing |
0% to 95%, non-condensing | 0% to 95%, non-condensing | |||
Operating Elevation | Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating | Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating | Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating | Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating | |||
Audible Noise | <55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides |
<55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides |
<55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides |
<55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides |
|||
Agency | |||||||
Surge Immunity | IEC/EN EN61000-4-5, Level 3, Criteria A | IEC/EN EN61000-4-5, Level 3, Criteria A | IEC/EN EN61000-4-5, Level 3, Criteria A | IEC/EN EN61000-4-5, Level 3, Criteria A | |||
Transportation | ISTA Procedure 1E | ISTA Procedure 1E | ISTA Procedure 1E | ISTA Procedure 1E | |||
Safety | IEC62040-1:2008 version, GS mark | IEC62040-1:2008 version, GS mark | IEC62040-1:2008 version, GS mark | IEC62040-1:2008 version, GS mark | |||
Emissions | IEC/EN/AS 62040-2 2nd Ed (Cat 2) | IEC/EN/AS 62040-2 2nd Ed (Cat 2) | IEC/EN/AS 62040-2 2nd Ed (Cat 2) | IEC/EN/AS 62040-2 2nd Ed (Cat 2) | |||
Warranty | |||||||
Std. 2 year; Opt. 1 and 3 year extension | Std. 2 year; Opt. 1 and 3 year extension | Std. 2 year; Opt. 1 and 3 year extension | Std. 2 year; Opt. 1 and 3 year extension |
GXT5-16KIRT9UXLE | GXT5-20KIRT9UXLE | ||||
Ratings (VA/W) | 16000 VA/16000 W | 20000 VA/20000 W | |||
Dimensions, mm (inches) | |||||
Unit W × D × H | 430×630×394 (16.9×24.8×15.5) |
430×630×394 (16.9×24.8×15.5) |
|||
Weight, kg (pounds) | |||||
Unit | 135.2 (298) | 135.2 (298) | |||
Input AC Parameters | |||||
Operating Frequency, Nominal | 50 or 60 Hz (factory-default is 50 Hz) |
50 or 60 Hz (factory-default is 50 Hz) |
|||
Voltage Range | 288 VAC | 288 VAC | |||
Input Wiring | Input terminal block | Input terminal block | |||
Output AC Parameters | |||||
Output Receptacles | Output terminal block, Optional Pods | Output terminal block, Optional Pods | |||
Factory-default VAC Frequency | 230 VAC, 50 Hz | 230 VAC, 50 Hz | |||
Waveform (On Battery) | Sinewave | Sinewave | |||
Utility (AC) Mode Overload | > 150% minimum 200 ms | > 150% minimum 200 ms | |||
Battery | |||||
Type | Valve-regulated, non-spillable, lead acid | Valve-regulated, non-spillable, lead acid | |||
Backup Time (100% Load) |
3.5 Minutes | 2.5 Minutes | |||
Backup Time (50% Load) |
9.5 Minutes | 7 Minutes | |||
+1 External Battery Cabinet (100% Load) | 10 Minutes | 7 Minutes | |||
+1 External Battery Cabinet (50% Load) | 26.5 Minutes | 19.5 Minutes | |||
Environmental Requirements | |||||
Operating Temperature,°C (°F) | 0 to 40 (+32 to +104) (no derating) | 0 to 40 (+32 to +104) (no derating) | |||
Storage Temperature,°C (°F ) | -15 to 40 (+5 to +104) | -15 to 40 (+5 to +104) | |||
Relative Humidity | 0% to 95%, non-condensing | 0% to 95%, non-condensing | |||
Operating Elevation | Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating | Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating | |||
Audible Noise | <58 dBA, at 1 meter from the front | <58 dBA, at 1 meter from the front | |||
Agency | |||||
Surge Immunity | IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62 41 Category B | IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62 41 Category B | |||
Transportation | ISTA Procedure 1E | ISTA Procedure 1E | |||
Safety | UL1778, c-UL listed | UL1778, c-UL listed | |||
Emissions | FCC Part 15 (Class A) | FCC Part 15 (Class A) | |||
Warranty | |||||
Std. 2 year; Opt. 1 and 3 year extension | Std. 2 year; Opt. 1 and 3 year extension |