SPECIFCATION
Technical specifications |
General |
UPS output power rating (1.0 p.f.) |
25,50,75,100,125,150,175,200kW |
Efficiency in double conversion mode |
>96% |
Efficiency in Energy Saver System (ESS) |
>99% |
Static bypass rating |
200kW |
External paralleling |
up to 4 units with HotSync technology |
UPS topology |
Double conversion |
UPS degree of protection |
IP20 |
Acoustic noise at 1 m,in 25 ºC ambient temperature |
<70 dBA in double conversion,<55 dBA in ESS |
Altitude (max) |
1000m above sea level at 40 ºC.Maximum 2000m with 1%derating per each add.100 m |
Input |
Rated input voltage |
220/380 V,230/400 V,240/415V 50/60 Hz |
Voltage tolerance -Rectifier input |
187 to 276V |
Voltage tolerance -Bypass input |
Rated voltage -15%/+10% |
Rated input frequency |
50 or 60 Hz,user configurable |
Frequency tolerance |
40 to 72 Hz |
Input wiring |
3 phase+neutral |
Input power factor at 100%load |
>0.99 |
Input ITHD |
<3% |
Rated input r.m.s current |
25kW |
50kW |
75kW |
100kW |
125kW |
150kW |
175kW |
200kW |
380V |
40A |
80 A |
120A |
159 A |
199 A |
239A |
278 A |
318 A |
400V |
38A |
76A |
114 A |
51 A |
189 A |
227 A |
264 A |
302 A |
415V |
37 A |
73 A |
110 A |
46 A |
182 A |
219 A |
255 A |
291 A |
Soft start capability |
Yes |
Intemal backfeed protection |
Yes |
Output |
Output wiring |
3 phase +neutral |
Rated output voltage rating |
220/380 V,230/400 V,240/415 V.configurable |
Total voltage harmonic distortion |
<1%(100%linear load);<3%(100%non-linear load) |
Output power factor |
1.0 |
Permitted load power factor |
0.8 lagging to 0.8 leading |
Overload on inverter |
10 min 102-110%,60 sec 111-125%,10 sec 126-150%,300 ms>150% |
Overload on bypass |
Continuous<125%,20 ms 1000% |
Battery |
Battery type |
12V,VRLA |
Charging method |
ABM technology or Float |
Temperature compensation |
Optional |
Battery nominal voltage (VRLA) |
480V |
Battery quantity |
36 to 44 blocks.Default is 40 blocks |
Charge current limit |
Default 5A,configurable maximum 25A per UPM |
Battery start capability |
Yes |
Communications |
Minislot |
3 communication bays |
Network/SNMP interface |
Yes,optional |
Serial ports |
Built-in host and device USB |
Standard connectivity ports |
Mini-slot ports for optional cards,Device USB and Host USB,RS-232 service port,relay output,
5 building alarm inputs and a dedicated EPO |
Accessorles |
MiniSlot connectivity (Web/SNMP,ModBus/Jbus,Relay) |
External Battery Cabinet(EBC) |
Parallel Tie Cabinet(PTC) |
External Maintenance Bypass Switches(EMBS) |
External Battery Cabinet Breaker(EBCB) |
Compliance with standards |
Safety |
IFC 62040-1 |
EMC |
EC 62040-2 |
Performance |
EC 62040-3 |
FAQ
1. May I take some samples to test before I placing the order?
Yes, we can offer sample testing for you to verify product quality and performance.
2. What is the warranty?
We support 1 years warranty.
3.What can you buy from us?
Eaton, Vertiv, APC, Santak, Vesion & OEM/ODM UPS; Cooling, MDC, PDU and so on.
4. What payment methods does your conmpany support?
We could accept T/T, credit card, Alipay or L/C at sight.
5. What are the terms can you offer for us?
We could offer EXW, FOB, CIF, DDP and so on.