| Customization: | Available |
|---|---|
| Phase: | Single Phase |
| Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
6-10kVA
| Model | PT 6K | PT 6KS | PT 10K | PT10KS | ||
| Output | ||||||
| Rated capacity | 6kVA | 6kVA | 10kVA | 10kVA | ||
| Power factor | 1 | |||||
| Rated voltage | 220V/230V/240V | |||||
| Voltage Tolerance | ± 1 % | |||||
| Rated frequency | (50/60±0.1) Hz | |||||
| System | Three-phase Single wire | |||||
| Output THDV(Linear load) | ≤1% | |||||
| Crest factor ratio | ≥3 | |||||
| Online dual conversion mode efficiency | 95% | 95% | 95% | 95% | ||
| Efficiency of economic model | 98% | 98% | 98% | 98% | ||
| Overload capacity | 125%,10 minutes | |||||
| Input | ||||||
| Voltage range | 110VAC-275VAC | |||||
| System | Single-phase, Three-wire | |||||
| Frequency range | 40~70Hz | |||||
| Power factor(PF) | >0.99 | |||||
| Input (THDi) | <3%(Single phase) | |||||
| Battery | ||||||
| Battery voltage | 192VDC (192V~240V adjustable) | |||||
| Max Charge Current | 0~4A adjustable(Default 1.4A) | 0~12A adjustable(Default 4A) | 0~4A adjustable(Default 2A) | 0~12A adjustable(Default 4A) | ||
| Charging temperature compensation | Support | Support | Support | Support | ||
| Backup time (time/load) | 11mn/2700W | - | 8mn/4500W | - | ||
| Recharge time | Charge back to 90% in 3 hours | - | Charge back to 90% in 3 hours | - | ||
| Communication and display | ||||||
| Display screen | LCD | |||||
| Communication interface | Standard USB, RS232, RPO, ROO, smart slot, dry node | |||||
| Size and weight | ||||||
| W×H×D(mm) | 438*86.3*573 | 438*86.3*573 | 438*86.3*573 | 438*86.3*573 | ||
| Rack mount height | 2U | |||||
| Net weight(Kg) | 14 | 14.4 | 15.9 | 16.3 | ||
| Working conditions | ||||||
| Type | Rack/Tower | |||||
| Temperature | 0 ºC ~ 50 ºC | |||||
| Humidity | 0 ~ 95% (Non-condensate) | |||||
| Altitude | 0~3000 meters, higher than 1000 meters need to reduce capacity. | |||||
| Noise | ≤50dB | ≤50dB | ≤55dB | |||
| Protection grade(IP) | IP20 | |||||
| Certification and standards | ||||||
| Standard | Safety:IEC/EN 62040-1 Electro magnetic compatibility(EMC):IEC/EN 62040-2, C3 Performance:IEC/EN 62040-3 |
|||||
| Certification | TLC/CE/CQC, Energy conservation | |||||
| Model | PT 10KS31 | PT15KS | PT20KS | |||
| Output | ||||||
| Rated capacity | 10kVA | 15kVA | 20kVA | |||
| Power factor | 1 | |||||
| Rated voltage | 220V/230V/240V | Single phase220V/230V/240V,Three phase 380V/400V/415V | ||||
| Voltage Tolerance | ± 1 % | |||||
| Rated frequency | (50/60±0.1) Hz | |||||
| System | Single-phase three-wire | Single-phase three-wire, three-phase five-wire | ||||
| Output THDV(Linear load) | ≤1% | |||||
| Crest factor ratio | ≥3 | |||||
| Online dual conversion mode efficiency | 95% | 96% | ||||
| Efficiency of economic model | 98% | 99% | ||||
| Overload capacity | 125%,10 minutes | |||||
| Input | ||||||
| Voltage range | Single phase 110VAC~275VAC, Three phase191VAC~476VAC |
Single phase 100VAC~300VAC, Three phase 173VAC~520VAC |
||||
| System | Single-phase three-wire, Three-phase five-wire | |||||
| Frequency range | 40~70Hz | |||||
| Power factor(PF) | >0.99 | |||||
| Input (THDi) | <3% | |||||
| Battery | ||||||
| Battery voltage | 192VDC (192V~240V default) | 384VDC (384V~480V default) | ||||
| Max Charge Current | 0~12A adjustable(default 4A) | 0-13A adjustable(default 2A) | ||||
| Charging temperature compensation | Support | |||||
| Communication and display | ||||||
| Display screen | LCD | |||||
| Communication interface | Standard USB, RS232, EPO, Smart slot, Dry node | |||||
| Size and weight | ||||||
| W×H×D(mm) | 438*86.3*573 | 438* 129* 589 | ||||
| Rack mount height | 2U | 3U | ||||
| Net weight(Kg) | 16.2 | 23.7 | ||||
| Working conditions | ||||||
| Type | Rack/Tower | |||||
| Temperature | 0 ºC ~ 50 ºC | |||||
| Humidity | 0 ~ 95% (Non-condensate) | |||||
| Altitude | 0~3000 meters, higher than 1000 meters need to reduce capacity. | |||||
| Noise | ≤50dB | |||||
| Protection grade(IP) | IP20 | |||||
| Certification and standards | ||||||
| Standard | Safety:IEC/EN 62040-1 Electro magnetic compatibility(EMC):IEC/EN 62040-2, C3 Electro magnetic compatibility(EMC):IEC/EN 62040-2, C3 Performance:IEC/EN 62040-3 |
|||||
| Certification | TLC/CE/CQC, Energy conservation | |||||



















1. May I take some samples to test before I placing the order?