Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Galaxy VS | 400V |
Topology | On-line double conversion |
Nominal power (kW) | 10-150 kW(parallel up to 600 kW)[4 UPSs in parallel] |
Key features | |
Scalability option | 50-150 kW |
N+1 redundancy option | 20-50 KW N+1 |
Modular elements | Power modules with Live Swap.static switch module.smart battery modules.intelligence module |
Display | Color touch screen.4.3 inches,status LED.mimic on display |
High priority for C&l | Network management card included with ethernet (SNMP)and modbus.8 dry contacts (4 inputs,4 outputs) |
Maintenance bypass | Internal maintenance bypass.Optional maintenance bypass panel |
Parallel capability | Simplified 1+1 parallel (for redundancy);Up to 4 UPSs in parallel for capacity or redundancy |
Ffficiency | |
Double conversion mode | Up to 97% |
ECO mode | Up to 99% |
ECOnversion mode | Up to 99% |
Input | |
Nominal input voltage | 3807400/415V |
nput voltage range (phase to phase) | +/-15% |
Single mains/dual mains | Single mains as standard.Easily converted to dual mains |
Input frequency | 40-70 Hz |
nput power factor | EC power factor:>0.99@load>25%,>0.95@load>15% |
Maximum short-circuit rating | 65 kA |
Backfeed protection | Included |
Output | |
Nominal output voltages | 380/400/415V |
Load power factor | PF=1 (0.7 leading to 0.7 lagging without derating |
Voltage regulation | +1-1% |
Frequency | 50/60 Hz+-0.1%free running |
Overload | 1 min @150%;10 min @125% |
Output THDU on linear load | <1% |
Battery type | VRLA.Lithium-io |
Nominal battery voltage,UPS for external batteries | 480-576V(at ratings 50 kW.100 kW.150 kW):60 kW:432-576;384-576V(at other ratings,including 60 kW and 120 kW) |
Nominal battery voltage.UPS with internal batteries | 480VDC |
Charging power | Charging power in %of output power at 0-40%load:80%:Charging power in %of output power at 100%load:20% |
Environment | |
Acoustic noise.UPS for external batteries | 57 dB(70%load)/65dB(100%load) |
Acoustic noise,UPS with internal batteries | 54-65 dB.depending on load percentage and model |
Dust protection | Air filter included.Conformal coated boards |
Seismic | With optional kit.OSHPD tested |
Environmental | Green Premium Certified.RoHS,Reach |