Customization: | Available |
---|---|
Type: | Cabinet Air Conditioner |
Air Tube Material: | FRP |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Outdoor condenser dimensions and weight | |||
Type | Mode | Dimensions(W*D*H mm) | Weight(kg) |
Standard air-cooled outdoor condenser Low temperature outdoor condenser |
DMC05WP1 | 787*352*829 | 40 |
DMC07WP1 | 787*352*829 | 40 | |
DMC12WP1 | 787*352*1240 | 61 | |
DMC17WT3 | 950*400*1245 | 85 | |
DMC22MT1 | 1133*520*1323(Vertical installation) 1305*1133*974(Horizontal installation) |
104 | |
DMC27MT1 | 1293*520*1491(Verticalinstallation) 1473*1293*974(Horizontal installation) |
120 | |
DML07WP1 | 1037*352*829 | 53 | |
DML12WP1 | 1037*352*1240 | 95 |
Specifications | |||||||
Model | DME05 | DME07 | DME12 | DME17 | DME22 | DME27 | |
Refrigeration capacity and sensible cooling capacity(kW) |
24ºC | 5.5 | 7.5 | 12.5 | 17 | 22 | 28.1 |
50%RH | 5 | 7 | 11.3 | 15.5 | 19.8 | 25.3 | |
Air supply method | Top air supply | Top air supply | Top air supply | Top air supply | Top /Downward | Top /Downward | |
Fan | Standard air volume(m³/h) | 2000 | 2000 | 3100 | 4300 | 6000 | 7300 |
Number of fans | 1 | 1 | 1 | 1 | |||
External static pressure(Pa) | 20~50 | 20~50 | 20~50 | 20~50 | 20~50 | 20~50 | |
Compressor | Quantity | 1 | 1 | 1 | 1 | 1 | |
Electric heating | Power(kW) | 3(Optional) | 3(Optional) | 3(Optional) | 5.5(Optional) | 6(Optional) | 6(Optional) |
Infrared humidifier | Humidification amount(kg/h) | 1.5(Optional) | 1.5(Optional) | 1.5(Optional) | 3(Optional) | 3(Optional) | 3(Optional) |
Dimensions(W*D*Hmm) | 510*38 | 5*1850 | 600*500*1975 | 750*650*1975 | 800*765*1975 | 850*835*1975 | |
Weight(kg) | 85 | 85 | 125 | 230 | 253 | 283 | |
Electrical parameters | Max.current(A) | 20 | 20 | 20 | 25 | 26.8 | 30.3 |
Circuit breaker | 32 | 32 | 32 | 40 | 40 | 40 | |
Cooling method | Optional type | Water cooling/Air cooling | Water cooling/Air cooling | Water cooling/Air cooling |